This voltage drop calculator determines the voltage drop across a circuit, particularly useful for long wire runs. It computes the voltage drop based on input parameters like voltage, current, wire size, conductor type, and circuit distance. Additionally, it calculates the voltage at the load and the percentage voltage drop.
How to Calculate Voltage Drop
Voltage drop calculation is grounded in one of the most fundamental electrical engineering principles: Ohm’s Law. Ohm’s Law posits that the voltage difference across a conductor is directly proportional to the current flowing through it and the conductor’s total resistance.
Voltage drop is determined by multiplying the current and the resistance within the conductor. This concept has led to the derivation of a straightforward formula for computing the voltage drop in a conductor.
You can accurately determine the voltage drop for a specific circuit and select the appropriate wire gauge to ensure the drop remains within acceptable limits.
According to the National Electrical Code, the voltage drop in a feeder circuit should not exceed 5%, and in a branch circuit, it should be limited to 3% or less.
Input Parameters:
Voltage: Enter the source voltage of the circuit.
- DC 12V, 24V, 48V
- Single-phase voltages are 115V or 120V
- Three-phase voltages are 208V, 230V, 240V, or 480V.
Amperes: Enter the maximum current (in amps) expected to flow through the circuit. For motor circuits, use the nameplate Full Load Amperage (FLA) multiplied by 1.25.
Wire Size: Select the wire size in American Wire Gauge (AWG) or kcmil.
Conductor: Choose between common conductor materials like Copper or Aluminum.
Distance: Input the one-way length of the wire in the circuit in feet.
Key Information:
- Conductor Temperature: Calculations are based on a conductor temperature of 75°C.
- Source Reference: NFPA 70, National Electrical Code, Chapter 9, Table 8.
Calculation Formulas:
Calculation Formulas:
Ohm’s Law: Voltage drop (Vd) is calculated as Vd=I×R, where I is current and R is resistance.
Single-Phase Circuits: Vd=(2×K×L×I)/Cm
Three-Phase Circuits: Vd=(1.73×K×L×I)/Cm
Where:
- Vd = Voltage Drop
- I = Current in Conductor (Amps)
- L = One-way Length of Circuit (Feet)
- Cm = Cross Sectional Area of Conductor (Circular Mils)
- K = Resistance in ohms of 1 circular mil foot of conductor (12.9 for Copper, 21.2 for Aluminum at 75°C)
AWG chart
AWG # | Diameter (inch) | Diameter (mm) | Area (kcmil) | Area (mm2) |
---|---|---|---|---|
0000 (4/0) | 0.4600 | 11.6840 | 211.6000 | 107.2193 |
000 (3/0) | 0.4096 | 10.4049 | 167.8064 | 85.0288 |
00 (2/0) | 0.3648 | 9.2658 | 133.0765 | 67.4309 |
0 (1/0) | 0.3249 | 8.2515 | 105.5345 | 53.4751 |
1 | 0.2893 | 7.3481 | 83.6927 | 42.4077 |
2 | 0.2576 | 6.5437 | 66.3713 | 33.6308 |
3 | 0.2294 | 5.8273 | 52.6348 | 26.6705 |
4 | 0.2043 | 5.1894 | 41.7413 | 21.1506 |
5 | 0.1819 | 4.6213 | 33.1024 | 16.7732 |
6 | 0.1620 | 4.1154 | 26.2514 | 13.3018 |
7 | 0.1443 | 3.6649 | 20.8183 | 10.5488 |
8 | 0.1285 | 3.2636 | 16.5097 | 8.3656 |
9 | 0.1144 | 2.9064 | 13.0927 | 6.6342 |
10 | 0.1019 | 2.5882 | 10.3830 | 5.2612 |
11 | 0.0907 | 2.3048 | 8.2341 | 4.1723 |
12 | 0.0808 | 2.0525 | 6.5299 | 3.3088 |
13 | 0.0720 | 1.8278 | 5.1785 | 2.6240 |
14 | 0.0641 | 1.6277 | 4.1067 | 2.0809 |
15 | 0.0571 | 1.4495 | 3.2568 | 1.6502 |
16 | 0.0508 | 1.2908 | 2.5827 | 1.3087 |
17 | 0.0453 | 1.1495 | 2.0482 | 1.0378 |
18 | 0.0403 | 1.0237 | 1.6243 | 0.8230 |
19 | 0.0359 | 0.9116 | 1.2881 | 0.6527 |
20 | 0.0320 | 0.8118 | 1.0215 | 0.5176 |
21 | 0.0285 | 0.7229 | 0.8101 | 0.4105 |
22 | 0.0253 | 0.6438 | 0.6424 | 0.3255 |
23 | 0.0226 | 0.5733 | 0.5095 | 0.2582 |
24 | 0.0201 | 0.5106 | 0.4040 | 0.2047 |
25 | 0.0179 | 0.4547 | 0.3204 | 0.1624 |
26 | 0.0159 | 0.4049 | 0.2541 | 0.1288 |
27 | 0.0142 | 0.3606 | 0.2015 | 0.1021 |
28 | 0.0126 | 0.3211 | 0.1598 | 0.0810 |
29 | 0.0113 | 0.2859 | 0.1267 | 0.0642 |
30 | 0.0100 | 0.2546 | 0.1005 | 0.0509 |
31 | 0.0089 | 0.2268 | 0.0797 | 0.0404 |
32 | 0.0080 | 0.2019 | 0.0632 | 0.0320 |
33 | 0.0071 | 0.1798 | 0.0501 | 0.0254 |
34 | 0.0063 | 0.1601 | 0.0398 | 0.0201 |
35 | 0.0056 | 0.1426 | 0.0315 | 0.0160 |
36 | 0.0050 | 0.1270 | 0.0250 | 0.0127 |
37 | 0.0045 | 0.1131 | 0.0198 | 0.0100 |
38 | 0.0040 | 0.1007 | 0.0157 | 0.0080 |
39 | 0.0035 | 0.0897 | 0.0125 | 0.0063 |
40 | 0.0031 | 0.0799 | 0.0099 | 0.0050 |
Additional Notes:
- The results are estimations and may vary based on wire condition, temperature, connector quality, etc.
- Voltage drop should ideally be less than 5% under full load for optimal performance.
- Voltage drop factors include wire material, size, length, and current carried.
- Ensure proper cable selection and adherence to bundling rules for accurate ampacity and voltage drop estimations.